美國(guó)vanguard CBCT斷路器線圈測(cè)試儀
美國(guó)vanguard CBCT斷路器線圈測(cè)試儀
產(chǎn)品價(jià)格:¥(人民幣)
  • 規(guī)格:CBCT
  • 發(fā)貨地:上海
  • 品牌:
  • 最小起訂量:1件
  • 誠(chéng)信商家
    會(huì)員級(jí)別:鉆石會(huì)員
    認(rèn)證類型:企業(yè)認(rèn)證
    企業(yè)證件:通過認(rèn)證

    商鋪名稱:上海山合海融商貿(mào)有限公司

    聯(lián)系人:孫寶金(先生)

    聯(lián)系手機(jī):

    固定電話:

    企業(yè)郵箱:sh@51082245.com

    聯(lián)系地址:上海市寶山區(qū)陸翔路678弄60號(hào)

    郵編:201907

    聯(lián)系我時(shí),請(qǐng)說是在五金機(jī)電網(wǎng)上看到的,謝謝!

    商品詳情

      The CBCT is a variable voltage DC power supply designed specifically to test substation circuit-breaker Open and Close coils. The CBCT uses the substation’s DC power supply to electronically generate a programmable output voltage from 5% to 95% of the source voltage. The CBCT can maintain up to an 80A test current while maintaining 2% or better voltage regulation during the circuit breaker coil operation.


      • One continuous and one pulse DC output
      • Back-lit LCD screen (20 characters by 4 lines)
      • Output voltage programmable from 5% to 95% of the input voltage
      • Built-in, single channel timer

      CBCT

      Technical Specifications

       
             
      TYPE Programmable DC Power Supply
      PHYSICAL SPECIFICATIONS 19”W x 7”H x 15”D, (48 cm x 17 cm x 38 cm); Weight: 25 lbs (11.3 kg)
      INPUT VOLTAGE 20 – 300 Vdc, 20A fuse
      OUTPUT VOLTAGE 5% – 95% of input voltage with 2% regulation at max current (up to 80A)
      OUTPUT VOLTAGE CHANNELS One continuous and one pulse DC output
      OUTPUT VOLTAGE PROTECTION Shutdown if current exceeds 80A or if current drawing time exceeds 500 ms @ 80A
      VOLT METER RANGE Input/output meters, 0 – 300 Vdc; Accuracy: 1% of reading, ±0.2V
      TIMER DISPLAY RANGE 0.0000 – 999.999 seconds; Accuracy: 0.01%, ±0.5 ms
      TIMER START INPUT Internal (coil initiation), wet-contact input (20 – 240 Vac/dc), or dry-contact input (1 – 200 ohms)
      TIMER STOP INPUT Wet-contact (20 – 240 Vac/dc) or dry-contact (1 – 200 ohms)
      DISPLAY Back-lit LCD screen (20 characters by 4 lines); viewable in both bright sunlight and low-light levels
      SAFETY Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
      ENVIRONMENT Operating: -10°C to 50°C (+15°F to +122°F); Storage: -30°C to70°C (-22°F to +158°F)
      CABLES Two 6-foot (#8 AWG) DC cable sets, Two 10-foot timer cable sets, One ground cable, one cable bag
      OPTIONS Transportation case
      WARRANTY One year on parts and labor
      Specifications are valid at nominal voltage and ambient temperature of +25?C (+77?F).